Back

GasGuard

GasGuard

The GasGuard gas proving system is designed to meet the requirements of IGEM/UP/11 Edition 2 for educational establishments and is a BS6173:2009 and IGEM/UP/19 compliant ventilation interlock.

The GasGuard is ideal for when appliances are not fitted with flame failure devices or can be used to provide additional peace of mind when they are.

With a backlit LCD, the GasGuard will provide a clear indication of any issues with external devices such as ventilation systems, and will provide details of gas pressures and Gas Sensor levels.

Downloads

View FileGasGuard - Gas Proving & Interlock System

Key Features

  • Clear LCD indication & instructions
  • No commissioning required
  • Annual Service Reminder
  • 24VDC auxiliary power output
  • Interfaces for:
    • Gas Sensors, CO2 Sensors, Ventilation Systems, Remote Emergency Stop Buttons
  • System status button to aid with fault finding
  • High accuracy Pressure Transmitter
  • Built in time delays to avoid nuisance tripping
  • 5 Year Warranty
  • UK MANUFACTURED

Technical Specification

Power Supply 100 -250VAC 50/60Hz
Consumption (Max) 40W
Power Output Gas Solenoid - Switched Mains
IP Rating IP65 (Providing rear entry sealed)
Approval CE

External Device Interfaces

Valve Status SPST - 5A @ 250V Max
Pressure Trans Monitors Proving Transmitter
24V Out Auxiliary Supply (300mA Max) for CO2T, FGS & FCMON
Gas Sensor BACnet Interface for Gas Sensors
CO2 Sensor 24V Signal to monitor external VFC
Intake Fan 24V Signal to monitor external VFC
Extract Fan 24V Signal to monitor external VFC
Remote Stop 24V Signal to monitor external VFC

Dimensions

Height 180 mm
Width 180 mm / 190 mm including Hinge
Depth 60 mm / 65 mm including Stop & Key Switch

Basic Operation

Turning the key switch to ON will start the proving cycle by energising the Gas Valve to pressurise the system, the valve will then close and the pipework is monitored for 30 seconds for pressure drops.

Upon receiving a fault signal from any external devices, the GasGuard will ensure that the gas is isolated to prevent any potential issues and the LCD will advise exactly what the issue is and how to rectify it.

Turning the key switch to the OFF position or pressing the panel stop button will isolate the gas supply.

The internal Open and Display buttons are also available to aid with commissioning and fault finding, providing details of ALL interfaces at the press of a button.


Installer Selectable Options

  • Gas Pipework Fill Time (5 or 10 Seconds)
  • Gas Availability Timer (Off, 4, 8 or 16 Hours)

Part Numbers & Options / Accessories

Part No Description
GG-PT00 GasGuard System c/w Pressure Transmitter

View our Gas Safety Solutions

View our Gas Safety Solutions

Not sure what you need?

Not sure what you need?

Ask one of our Experts

Ask one of our Experts

Call us on... 01925 281 230