Key Features
- Can connect with up to 16 Gas Sensors
- Clear LCD Indication
- Proving or Non-proving selectable
- Auto-reset following power failure
- Fire alarm test bypass timer
- 24VDC auxiliary power output to power 4-6 Flamefast Gas Sensors dependant on sensor type. External power supply required for additional.
- Additional Interfaces for:
- Thermal Links, Ventilation Systems, Remote Emergency Stop Buttons and Fire Alarm Systems
- Sensor calibration reminder
- Alarm 1, Alarm 2 and Fault relays
- Selectable relay latching function
- 5 Year Warranty
- UK MANUFACTURED
Technical Specification
Power Supply | 100 - 250 VAC 50/60 Hz |
Consumption (Max) | 40W |
Outputs | Gas Solenoid - Switched Mains |
Alarm 1 - SPDT - 5A @ 250V Max | |
Alarm 2 - SPDT - 5A @ 250V Max | |
Fault - SPST - 5A @ 250V Max | |
IP Rating | IP65 |
Approval | CE |
External Device Interfaces
24V Out | Auxiliary Supply (300mA Max) for FGS |
Pressure Trans | Monitors Proving Transmitter |
Gas Sensor | BACnet Interface for Gas Sensor |
Ventilation | 24V Signal to monitor external VFC |
Thermal Link | 24V Signal to monitor external VFC |
Fire Alarm | 24V Signal to monitor external VFC |
Remote Stop | 24V Signal to monitor external VFC |
Dimensions
Height | 180 mm |
Width | 180 mm / 190 mm including Hinge |
Depth | 60 mm / 65 mm including Stop Button |
Basic Operation
The BoilerGuard has three buttons on the front:
Reset - The BoilerGuard Alarm 1 and 2 relays are activated depending on the sensor conditions. Following an alarm the reset button can be used to reset any relays that are set to latch including the Gas Valve output which will shut down if any sensor reaches Alarm 2..
Mute - If there are any gas alarms, this can be used to silence the panel for 15 minutes. If this is held in for 10 seconds, this will also reset any non-latching alarm relays for 2 minutes.
Test - The operation of the Test button is dependent on the panel status:
- If the panel is live without any alarm conditions, holding this button in for 10 seconds will enable the Fire Alarm bypass. The Fire Alarm interface will be ignored for 30 minutes to allow tests to be carried out.
- Following an alarm (prior to reset), holding the Test button for 5 seconds each will change the state of the Alarm 1, Alarm 2 and Fault relays.
Installer Selectable Options
- Proving or Non-proving
- Auto-reset
- Alarm 1 Latching
- Alarm 2 Latching
Part Numbers & Options / Accessories
Part No | Description |
BG-PO | BoilerGuard Panel (Non-proving) |
BG-PT00 | BoilerGuard c/w Pressure Transmitter (Proving) |