Back

Flamefast Gas Sensor (FGS)

Flamefast Gas Sensor (FGS)

The Flamefast Gas Sensor is one of the most versatile gas sensors available on the market. With an Analogue and Relay output, as well as a BACnet MS/TP interface, FGS can connect directly into most third-party controllers or can easily connect to any of the Flamefast range of gas safety systems.

In a large proportion of modern buildings, the plant room safety systems are BMS integrated, and the FGS has been designed with this in mind. It can be treated like any other field sensor, the latching facility allows direct integration with the primary safety circuit, then simply pulse the Digital Input, or reset over the BACnet network once the alarm has cleared. This negates the requirement for a controller, cutting down cost of the equipment and installation.

The broadband Pellistor and Infra-red Hydro-carbon sensors can be calibrated to suit most combustible gases with the option to factory callibrate and rename the sensor for the specific gas. Flamefast can also offer a full of toxic gas sensors, including H2S, HCN and many more (please contact for details).

Downloads

View FileFlamefast Gas Sensor (FGS)

Key Features

  • 24V AC/DC Power Supply
  • Pre-calibrated
  • Traffic light LCD readout
  • Volt Free Contact output
  • BACnet MS/TP over RS485
  • Latching function with Reset input
  • Analogue output
  • Simple configuration and calibration
  • Calibration and ‘End of Life” Reminder
  • Oxygen Sensor monitors for Enrichment and Depletion as standard
  • Mounts onto any standard Single Gang Junction Box or Conduit Box
  • UK MANUFACTURED

Installer Selectable Options

  • LCD backlight - Enable/Disable
  • Failsafe option:
    • Energise/De-energise Relay
    • 0-10V or 2-10V
  • Alarm Latching - Enable/Disable
  • Audible Alarm - Enable/Disable
  • Auto Zero Calibration - Enable/Disable
  • Alarm 1, Alarm 2 & Relay set-points
  • Analogue Output Range
  • Display Gas Concentration or Gas Formula

Dimensions

Height 125 mm
Width 86 mm
Depth 36 mm

Technical Specification

Power Supply 24V AC/DC ±10%
Power Consumption 100mA
BACnet MS/TP 9k6, 19k2, 38k4 or 76k8
RS485 (1/10th Load)
Max 127 Addresses
Analogue Output 0/2-10V Full Scale Linear
VFC Output Rating SPDT - 1A @ 24V Max
Warm-up Time 60 seconds (24 Hours for full stability)
Response Time (T90) < 60 seconds (adjustable)
Operating Conditions Temp 5-40°C
Humidity 0-95% (NC)
Sampling Method Diffusion
IP Rating IP40
Housing Material Flame Retardant PC/ABS
Colour Pure White (RAL9010)
Approval UKCA,CE

Part Numbers & Options / Accessories

Part No Description Range Life
(ppm) (years)
FGS-NG Natural Gas (Methane) 100% LEL 5
FGS-LPG Propane 100% LEL 5
FGS-H2 Hydrogen (LEL) 100% LEL 5
FGS-HC Hydro-carbon (Pellistor) 100% LEL 5
FGS-IRHC Hydro-carbon (Infra-red) 100% LEL 5
FGS-SF6 Sulfur Hexafluoride 1,000ppm 5
FGS-CO2 Carbon Dioxide 5% 5
FGS-CO Carbon Monoxide (Plant/Carpark) 200ppm 5
FGS-NO2 Nitrogen Dioxide 5ppm 3
FGS-NH3 Ammonia 100ppm 3
FGS-CL2 Chlorine 5ppm 3
FGS-H2e Hydrogen (Electrochemical) 2,000ppm 3
FGS-SO2 Sulphur Dioxide 5ppm 3
FGS-O2 Oxygen 25.0% 5
OTHER GASES AVAILABLE ON REQUEST