Key Features
- 24V AC/DC Power Supply
- Pluggable terminal block for ease of installation
- Optional traffic light readout
- 3x 0-10V outputs
- Selectable Temperature output (0-10V or 10K3)
- Volt free contact output
- Typical 10+ year life expectancy
- Self-calibrating CO2 sensor
- Mounts onto any standard single gang junction box or conduit box
- UK MANUFACTURED
Technical Specification
Power Supply | 24V AC/DC ±10% |
Power Consumption | 50mA Max |
Analogue Outputs | 3x 0-10V |
VFC Output | SPST - 100mA @24V Max |
CO2 Range | 0 - 2,000ppm |
CO2 Accuracy | ±40ppm +3% @NTP |
CO2 Display Resolution | 1ppm |
CO2 Sensing Method | Non Dispersive Infra-red (NDIR) |
CO2 Typical Sensor Life | 10+ years |
Temp Range (0-10V) | 0 - 50°C |
Temp Accuracy | ±0.3°C @ 25°C |
RH Range | 0 - 100% |
RH Accuracy | +/-2% @ 20 - 80% |
Operating Conditions | Temp 0°C to 50°C |
Humidity 0 to 95% (NC) | |
Sampling Method | Diffusion |
Warm-up Time | 30 seconds |
IP Rating | IP66 (external to duct) |
Housing Material | Flame Retardant ABS/PC |
Approval | CE |
Dimensions
Height | 152 mm |
Width | 110 mm |
Depth | 50 mm |
Probe Length | 200 mm |
Installer Selectable Options
The unit has two user selectable programmes to control the volt free contact set point depending on the application.
These are as follows:
Program | Ventilation | Gas Safety | Relay Position | Normally Open | Normally Closed |
---|---|---|
Relay Set Point | 1,000ppm | 4,500ppm |
Part Numbers & Options / Accessories
Part No | Description |
---|---|
DTR-CO2 | Duct Transmitter - CO2 |
DTR-CO2TH | Duct Transmitter - CO2, Temp & RH |
DTR-TH | Duct Transmitter - Temp & RH |