Back
Key Features
- 24V AC/DC Power Supply
- Pre-calibrated
- Traffic light LCD readout
- BACnet MS/TP over RS485
- Simple configuration and calibration
- Calibration and ‘End of Life” Reminder
- Oxygen Sensor monitors for Enrichment and Depletion as standard
- Mounts onto any standard Single Gang Junction Box or Conduit Box
- UK MANUFACTURED
Installer Selectable Options
- Sounder Enable/Disable
- Auto-zero Enable/Disable
Dimensions
Height | 125 mm |
Width | 86 mm |
Depth | 36 mm |
Technical Specification
Power Supply | 24V AC/DC ±10% |
Power Consumption | 60mA |
BACnet MS/TP | 9k6, 19k2, 38k4 or 76k8 |
RS485 (1/10th Load) | |
Max 127 Addresses | |
Warm-up Time | 60 seconds (24 Hours for full stability) |
Response Time (T90) | < 60 seconds (adjustable) |
Operating Conditions | Temp 5-40°C |
Humidity 0-95% (NC) | |
Sampling Method | Diffusion |
IP Rating | IP40 |
Housing Material | Flame Retardant PC/ABS |
Colour | Pure White (RAL9010) |
Approval | UKCA,CE |
Part Numbers & Options / Accessories
Part No | Description | Range | Life |
---|---|---|---|
(ppm) | (years) | ||
FGD-NG | Natural Gas (Methane) | 100% LEL | 5 | FGD-LPG | Propane | 100% LEL | 5 |
FGD-H2 | Hydrogen (LEL) | 100% LEL | 5 |
FGD-HC | Hydro-carbon (Pellistor) | 100% LEL | 5 |
FGD-IRHC | Hydro-carbon (Infra-red) | 100% LEL | 5 |
FGD-SF6 | Sulfur Hexafluoride | 1,000ppm | 5 |
FGD-CO2 | Carbon Dioxide | 5% | 5 |
FGD-CO | Carbon Monoxide (Plant/Carpark) | 200ppm | 5 |
FGD-NO2 | Nitrogen Dioxide | 5ppm | 3 |
FGD-NH3 | Ammonia | 100ppm | 3 |
FGD-CL2 | Chlorine | 5ppm | 3 |
FGD-H2e | Hydrogne (Electrochemical) | 2,000ppm | 3 |
FGD-SO2 | Sulphur Dioxide | 5ppm | 3 |
FGD-O2 | Oxygen | 25.0% | 5 |
OTHER GASES AVAILABLE ON REQUEST |